CONSTRUCTION OF FCU CASING
• Robust construction casing
• Casing material – Galvanised steel hot dipped 1mm thick, fan plate 1.5mm thick
• Heavy duty fixing cleats as standard
• Full width removable access panels underneath
SPIGOT CONNECTIONS
• Insulated discharge plenum with 200dia or 250dia spigots
FANS AND MOTORS
• EBMPAPST GreenTech EC centrifugal fans are highly efficient, use up to 70% less energy than conventional AC fans and are extremely quiet.
• EBMPAPST GreenTech EC range of centrifugal fans with Active PFC (Power Factor Correction) achieves a power factor of up to λ = 0.99
• Each fan has plug and play quick release connectors, low running noise and SFP levels
INSULATION
• The unit is internally lined throughout with 10mm thermal and acoustic insulation with 90kg/m3 impregnated flexible PU foam rated to BS476 Parts 6 & 7; Class ‘0’ to building regulations
• Condensate trays are externally lined with 6mm insulation
CONDENSATE TRAY AND EXTENDED DRIP TRAY
• Condensate drip tray is manufactured from hot dipped galvanised steel with epoxy paint coating or stainless steel (optional)
• Fully welded corners with positive fall to drain and finished with a 22mm diameter copper tail at its lowest point
• Extended drip tray covers the entire length of the valve kit area
FILTER AND FILTER ARRANGEMENT
• EU1 as standard
• EU2 and EU3 available upon request
• Quick release filter via thumb screws – no tools required!
• Bespoke filter arrangements available upon request
COILS
• Heating and cooling coils Cu/Al
• Seamless copper tube
• Coil connections at 40mm centres to facilitate PICV valves
• Leak tested with dry air under water to 16 bar pressure
POTENTIOMETER AS STANDARD
• Each OPTIMUM FCU comes with a potentiometer mounted externally on the control box, c/w dial with visual settings marked 1-10
CONTROLS AND ACCESSORIES
• Ventilated controls enclosure
• Low voltage transformer
• Hand/Auto Switch on FCU as standard
• PICV & Actuator (optional)
• BMS controller (optional)
• Return & supply air temperature sensor (optional)
• Local wall controller (optional)
• Condensate pump (optional)